• BUILDING RELATIONSHIPS... THROUGH PERFORMANCE

APPLICATIONS

Designed to maintain circuit integrity during a fire and ensure maximum time for evacuation in case of an emergency. Typically used in fire alarm systems, emergency lighting and other safety equipment.

TYPES & SIZES

Single-core up to 1000 sq.mm and Multi-core up to 400 sq.mm for voltage up to 3.3 kV

Aluminium – Solid, Stranded (Sector/Circular) or Copper – Solid, Stranded (Sector/Circular) or Flexible – Bare or Tinned

Glass Mica Tape over the Conductor

PVC, XLPE, EPR with additional taping or screening (if required)

PVC, PE, LSZH or Rubber—HR/HOFR

Galvanized Steel Wire / Flat Strip or GI / Tinned Copper Braid

SPECIFICATION

IEC: 60502-1, BS: 7846 or equivalent, BS: 6387 Category (CWZ),

IEC: 60331, BSEN 50200 (PH30, PH60, PH120 & Annex E)

KEY FEATURES

  1. Cables withstand 650° C for 3 hours (Category A), 750° C for 3 hours (Category B), 950° C for 3 hours (Category C) with resistance to fire with water and mechanical shock (Category CWZ)
  2. High resistance to fire & toxic gases with low emission
  3. Ease and low cost of installation
  4. Customization options available